An installation consists of a 10-kVA, single-phase transformer with a 440-volt primary and a 110-volt, 2-wire secondary using THWN with copper conductors with no secondary OCPD installed. Calculate the maximum standard size OCPD permitted by Table 450.3(B) to protect the primary of the transformer where the secondary conductors are 3 AWG THWN copper

ansver
Answers: 2

Another question on Mathematics

question
Mathematics, 21.06.2019 17:30
Aplot of land is shaped like a quadrilateral. fences are built on the diagonal to divide the area into 4 sections. what is vi to the nearest tenth? gv = 6.55fv = 5.84vh = 3.27vi = ?
Answers: 1
question
Mathematics, 21.06.2019 21:00
How do i put 3(x+7) in distributive property
Answers: 2
question
Mathematics, 21.06.2019 23:30
Asap (i need to finish this quick) graph complete the sequence of transformations that produces △x'y'z' from △xyz. a clockwise rotation ° about the origin followed by a translation units to the right and 6 units down produces δx'y'z' from δxyz.
Answers: 1
question
Mathematics, 22.06.2019 00:30
Astrid spent $36 on new shoes. this was $12 less than twice what she spent on a new skirt. part a: which equation would solve for how much she spent on the skirt? part b: solve the equation in the workspace provided below. how much did astrid spend on her skirt?
Answers: 1
You know the right answer?
An installation consists of a 10-kVA, single-phase transformer with a 440-volt primary and a 110-vol...
Questions
question
Mathematics, 14.09.2021 05:50
question
English, 14.09.2021 05:50
question
English, 14.09.2021 05:50
question
Mathematics, 14.09.2021 05:50
question
Mathematics, 14.09.2021 05:50
Questions on the website: 13722363