Atransformer connected to a 120-v (rms) ac line is to supply 13,000 v (rms) for a neon sign. to reduce shock hazard, a fuse is to be inserted in the primary circuit; the fuse is to blow when the rms current in the secondary circuit exceeds 8.50 ma. what current rating should the fuse in the primary circuit have?